15 KVA Diesel Generating Set
MEERACO 15 KVA DIESEL GENERATING SET A SERIES
Meeraco, we, are a diesel generating sets industry leader for performance, build quality, reliability, longevity and safety. Our generating sets are specially designed to withstand the harsh Indian environment and usage. Our silent diesel generating sets are especially reliable, fuel efficient and incredible value for money. We have state-of-art manufacturing unit in Ludhiana and an established after sales network across northern India.( Punjab, Haryana, Delhi )
Meeraco diesel generating sets are powered by the renowned Meeraco diesel engines conforming to the latest CPCB emission norms, are environment friendly and engineered to run under strenuous conditions.
STANDARD SCOPE ENGINE:
Meeraco diesel generating sets, powered by Meeraco engines of A Series, are rated at 1500 RPM. The engines are radiator cooled, four stroke and multi-cylinder, conforming to BS 5514 / ISO 3046 / ISO 8528.
THE SCOPE OF SUPPLY INCLUDES:
- Electrical starter motor 12V DC
- Battery charging alternator
- Bosch fuel system with mechanical governor
- Dual fuel filter
- lob oil filter
- Residential silencer
- Dry type air cleaner
- Coolant Reservoir
- Shut-off coil with safeties for LLOP/HWT
- First fill of lube oil and coolant
Diesel Generator Set Specifications
Make |
Meeraco |
Meeraco |
Phase |
1 Ph |
3 Ph |
Rating KVA |
15 |
15 |
Rated KW |
12 |
12 |
Rated Current (Amps) |
63 |
21 |
Power Factor |
0.8 (lag) |
0.8 (lag) |
Weight ( Kg ) |
800 |
800 |
Engine Specifications
Make |
Meeraco |
Meeraco |
Model |
A-1921G |
A-1921G |
BHP |
25.5 |
25.5 |
Working Principle |
4 Stroke |
4 Stroke |
Layout of Cylinders |
In-line |
In-line |
Firing Order |
1-2 |
1-2 |
No. of Cylinders |
2 |
2 |
Bore x Stroke ( mm ) |
105×118 |
105×118 |
Displacement ( Ltrs. ) |
2.044 |
2.044 |
Rated Speed ( RPM ) |
1500 |
1500 |
Compression Ratio |
18:1 |
18:1 |
Governor Type |
A1-Class |
A1-Class |
SFC (Gms/Bhp-Hr ) |
165 |
165 |
Lub oil specification |
CF 4 – 15 W 40 |
CF 4 – 15 W 40 |
Lub. Oil Consumption (%) |
0.1 |
0.1 |
Aspiration |
Natural |
Natural |
Oil Sump Capacity ( Ltrs.) |
6 |
6 |
Cooling |
Water Cooled |
Water Cooled |
Coolant Capacity ( Ltrs.) |
10 |
10 |
Exhaust pipe size ( mm ) |
65 |
65 |
Size ( mm ) |
675x555x795 |
675x555x795 |
Weight ( Kg ) |
255 |
255 |
Emission Compliance |
as per ISO 8178 (Part-3 ) |
as per ISO 8178 (Part-3 ) |
Battery Rating V/AH |
12V/88AH |
12V/88AH |
Fuel Tank Capacity ( Ltrs.) |
60 |
60 |
Alternator Specifications
Voltage ( V) |
230 |
415 |
Frequency ( Hz) |
50 |
50 |
Power Factor |
0.8 (lag) |
0.8 (lag) |
Class of Insulation |
H Class |
H Class |
Voltage Regulation |
+/- 1% |
+/- 1% |
Recommended Cable-Al.armoured cable (core x mm2) |
2×25 |
3.5×16 |
Canopy Specifications
Type |
Bolted |
Bolted |
Sheet Metal |
CRCA |
CRCA |
Insulation |
Foam/Rockwool |
Foam/Rockwool |
Paint |
7 Tank Process Powder Coat |
7 Tank Process Powder Coat |
Noise Level at 1 M |
75 dba |
75 dba |
Size ( mm ) |
1900x1000x1400 |
1900x1000x1400 |
MEERACO SERIES ENGINE FEATURES AND BENEFITS :
- Meeraco series DG sets are smaller and lighter than any other DG set in it’s class, thus giving you the advantage of optimizing your valuable space.
- Low exhaust emission , meets the next generation CPCB norms thus offering you environment friendly power.
- Wet liner construction eliminates time consuming and expensive block re-boring during overhauls.
- Deep skirted crank case design , high degree of rigidity and ruggedness.
- Easy accessibility of all maintenance parts.
- High degree of commonality of components over entire range.
- Individual cylinder head design , savings on maintenance cost and time.
- Simple inline fuel injection pump.
- High reserve power margins for providing higher block load capability.
- Very low basic engine noise level.
ALTERNATOR:
Meeraco alternator, suitable for operation at 1500 RPM, 415 Volts,0.8 pf (lag) suitable for 50 Hz, 3 phase & 1 phase, 4 wire & 2 wire system. The alternator is designed and built to withstand tropical conditions. The alternator generally conforms to IEC 34-1/34-2, BS 4999/5000 and IS: 4722-2001 with enclosures rating IP 23 is the standard version, satisfying IEC 34-5/IS: 4691/DIN VDE 0530-5 requirements. The Alternator is dynamically balanced, brushless type, screen protected, revolving field, self excited, self regulated through an AVR. The alternator has the following features:
- +- 1.0 % Voltage regulation (max.) in static conditions
- IP: 23 protection with insulation class H
- Permissible overload of 10% for one hour in 12 hours of operation.
MOUNTING ARRANGEMENT:
Engine and alternator are mounted on a common MS fabricated base frame with AVM pads.
CONTROL PANEL:
The gensets are supplied with inbuilt control panels complete with internal wiring/cabling having necessary displays and protections for ease of operation and maintenance. The control panel is manufactured with 14/16 gauge CRCA sheet and is powder coated for weather-proof and long lasting finish.
THE CONTROL PANEL CONSISTS OF THE FOLLOWING PARTS:
- Microprocessor Controller
- Kew Switch
- Aluminum bus bars with suitable capacity with incoming/outgoing terminals.
- Indicating lamps for Load On and Set Running.
- MCB/MCCB of suitable rating with overload and short circuit protections
- Current Transformers.
THE CONTROLLER :
The controller is a microprocessor based generator set monitoring and control system. The control provides a simple operator interface to the generator set, manual and extended wire remote start/stop control, shutdown fault indication, and an LCD hour counter. The integration of all functions into a single control system provides enhanced reliability and performance compared to conventional generator set control systems. This control has been designed and tested to meet harsh environment in which gensets are typically applied.
MONITORING SYSTEM:
Multifunction meter displaying the following parameters:
- Generator A.C. Voltage
- Generator Current
- Generator Frequency
- Engine Coolant Temperature
- Engine Lube oil Pressure
- Fuel Level
- Generator
- Battery Voltage
- Engine Running Hours
- Service Due Hours
CONTROL SYSTEM:
The standard control system includes all the functions necessary to locally or remotely start and stop and protect the generator set.
KEY SWITCH :
OFF/ ON /START
In the OFF mode the generator set will remain in sleep mode. In ON position the control is powered and the start/stop push buttons become enabled. DG Set can also be started with key switch manually.
LED INDICATING LAMPS:
The control includes LED lamp indication for the following functions:-
- Failed to start
- Over speed/Under speed
- Low oil pressure
High water Temp.-Battery Chg. Alt. fail-Radiator water level-Over voltage -Under frequency-Over frequency under voltage-Over current
LCD ENGINE HOUR COUNTER:
The control includes an LCD engine hour counter. The counter will increment whenever the engine is running. There is also a provision for service hour settings.
ENGINE SAFETY AND PROTECTION FEATURES:
Fail safe system with special sensor to safeguard Diesel generator against faults like:
- Emergency stop: Annunciated whenever an emergency stop signal is received by the control.
- Low lube oil pressure
- High water temp
- Low and high battery voltage
- Short circuit protection
- Over speed protection
Alternator Protective functions includes
- High and Low AC voltage.
- Under and Over frequency
- Loss of sensing voltage input
ACOUSTIC ENCLOSURE:
The acoustic enclosure is made of 1.6/ 2 mm thick CRCA sheets in green shade and a structural/ sheet metal base frame painted in black. The walls of the enclosure are insulated with fire retardant foam so as to comply with the 75 dBA at 1 mtr sound levels specified by Ministry of Environment & Forest. Enclosure has the following features:
- Specially designed to meet stringent MOEF/ CPCB norms of 75 dBA @ 1mtr under free field conditions
- The compactness of the enclosures make it an ideal choice for customers having space constraints.
- Designed to have optimum serviceability
- Built-in fuel tank of adequate capacity ( suitable for 12 hrs. of operation )
- Air inlet louvers specially designed to operate at rated load
- Made on special purpose CNC machines for consistency in quality and workmanship
- External fuel filling with fuel level indicator
- Powder coated for long lasting service life and superior finish
- With UV resistant powder coating, can withstand extreme environments.
- Use of special hardware for longer life
- Insulation material meets exacting IS 8183 specifications for better sound attenuation.
- Fluid drains for lube oil and fuel
- Fuel filling point
- All doors lockable with common key
OPTIONALS
AMF control panel consists of microprocessor based AMF control unit, which can operate on auto, as well as manual mode. It monitors the engine safety parameters and alarm /trip conditions will be displayed on the front panel.
- Trolley mounted mobile sets
- Cold starting kit
TECHNICAL DATA
Generator set specifications:
**Due to our continuous product improvement efforts, the specifications in this brochure are subject to change without prior notice. *Fuel consumption of Genset is considering specific gravity of fuel as 0.8355 at NTP conditions and alternator efficient of 91-93%. SFC subject to tolerance of +5%. *Fuel: HSD (IS 1460), calorific value of fuel : 10,500 Kcal/Kg. *Conformance standards: Rating as per BS 5514/ISO 3046/ ISO 8528.
Author Rating
Aggregate Rating
4.5 based on 12 votes
Brand Name
Meeraco
Product Name
15 KVA Diesel Generating Sets